CopperOn CS600 is a Modular UPS system that combines high AC/AC efficiency values with a compact footprint and a flexible and scalable architecture.
CS600 UPS can start with a basic configuration of just 30 kVA and then grow gradually as required, up to 900 kVA.
The CS600 models offer input PF 0.99 and input THDi < 3 %, even when a low percentage of load is applied. The system can reach the highest AC/AC efficiency levels available, of up to 98.5 % in ECO Mode. The flat efficiency curve from 35 % of load will ensure maximum energy savings at every percentage of load.
As well as all other critical applications where power reliability is essential and power consumption is an important variable.
|
Model |
CS600 |
CS600 |
CS600 |
|
Frame model |
Frame 180 |
Frame 300 |
Frame 600 |
|
Maximum capacity (kVA) |
180 |
300 |
540 (+ redundancy) |
|
Maximum number of power modules connected |
6 |
10 |
20 |
|
Parallel operation |
Up to 3 frames |
Up to 3 frames |
No |
|
Dimensions W x D x H (mm) |
600 x 1100 x 1600 |
600 x 1100 x 2000 |
2000 x 1100 x 2000 |
|
Weight (kg) |
165 |
220 |
660 |
|
Color of the frame |
RAL 7021 |
|
|
|
Power Module |
|
|
|
|
Nominal power (kVA / kW) |
30 / 27 |
|
|
|
Dimensions W x D x H (mm) |
460 x 790 x 134 |
|
|
|
Weight (kg) |
34 |
|
|
|
Input |
|
|
|
|
Phase |
3Ph + N + G |
|
|
|
Nominal voltage (V) |
380 / 400 / 415 |
|
|
|
Voltage range (V) |
304 to 478 V (at full load) ; 228 to 304 V (with load decreasing linearly) |
||
|
Frequency (Hz) |
50 / 60 |
|
|
|
Frequency range (Hz) |
40 / 70 |
|
|
|
Power factor |
0.99 |
|
|
|
Input THDi |
<3 % (with linear load) |
|
|
|
Output |
|
|
|
|
Voltage (V) |
3Ph + N: 380 / 400 / 415 |
|
|
|
Voltage regulation |
1.5 % |
|
|
|
Output THDv |
<1 % (with linear load), <6 % (with nonlinear load) |
|
|
|
Output PF |
0.9 |
|
|
|
Crest factor |
3:1 |
|
|
|
Frequency (Hz) |
50 / 60 |
|
|
|
Overload capacity |
110 % for 60 min, 125 % for 10 min, 150 % for 1 min, 150 % for 200 ms |
||
|
AC/AC efficiency in double conversion (VFI) |
Up to 95.5 % |
|
|
|
AC/AC efficiency in ECO Mode (VFD) |
Up to 98.5 % |
|
|
|
Battery Line |
|
|
|
|
Nominal DC voltage (VDC) |
±240 (with +/N/- connections) |
|
|
|
Quantity of lead acid batteries (12 V each) |
40 (settable from 32 to 44) |
|
|
|
Recharge power |
10 % system power (nominal value); Settable: from 0 to 20 % system power |
||
|
Temperature compensation (mV / ° C) |
-3.0 (selectable: 0 to -5.0) |
|
|
|
User Interface |
|
|
|
|
Display |
10.4'' LCD + LED, Color touch screen + Keyboard |
|
|
|
IP protection degree |
IP20 |
|
|
|
Standard communication ports |
RS232; RS485, Dry contacts, USB |
|
|
|
Optional communication ports |
SNMP, Expansion Dry contact card |
|
|
|
Environmental |
|
|
|
|
Operating temperature (° C) |
0 to 40 |
|
|
|
Storage temperature (° C) |
-40 to 70 |
|
|
|
Relative humidity |
0 to 95 % |
|
|
|
Noise at 1 m distance (dB) |
65 (with nominal load); 62 (with 45 % of load) |
|
|
|
Standards & Certifications |
|
|
|
|
Safety |
IEC EN 62040-1 |
|
|
|
EMC |
IEC EN 62040-3 |
|
|
|
Test and performance |
IEC EN 62040-3 |
|
|